All calculators

Inspection, test & fault finding

UK cable resistance, R1+R2, R1+Rn and length from resistance

Every standard UK conductor size with its resistance in milliohms per metre, a forward query that turns a run length into expected R1+R2 and R1+Rn values, and a reverse query that turns a measured reading back into a distance — the quickest way to work out roughly how far along a circuit a fault or a junction actually sits.

Query 1 — length ➝ R₁+R₂ and R₁+Rₙ

Expected readings for a run

Pick the cable, enter the one-way route length and the calculator returns the expected end-to-end R1, Rn, R2, R1+R2 and R1+Rn for a radial circuit.

Results

Line 2.5 mm² resistance7.41mΩ/m
Neutral 2.5 mm² resistance7.41mΩ/m
CPC 1.5 mm² resistance12.1mΩ/m
R₁ — line0.111Ω
Rₙ — neutral0.111Ω
R₂ — cpc0.181Ω
R₁+Rₙ expected0.222Ω
R₁+R₂ expected0.293Ω

Query 2 — measured reading ➝ length

Distance from a measured reading

Enter the reading you actually measured (R1+R2 or R1+Rn), pick the cable type and the calculator returns the equivalent cable length. Useful for locating a buried joint, an unexpected spur, or confirming whether a reading is plausible for the run you can see.

Results

R₁+R₂ loop per metre0.0195Ω/m
R₁+Rₙ loop per metre0.0148Ω/m
Equivalent cable length from R₁+R₂17.9m
If reading is a ring leg / return path9.0m

A reading noticeably higher than the visible run length usually means a loose or high-resistance connection, an undisclosed spur, or a smaller conductor than assumed. Re-null the leads and repeat before drawing conclusions.

Reference table

UK conductor resistance at 20 °C (mΩ/m)

Resistance per metre of standard UK copper and aluminium conductor sizes at 20 degrees Celsius
SizeCopper mΩ/mAluminium mΩ/mCopper Ω per 10 m
1.0 mm²18.10.1810
1.5 mm²12.10.1210
2.5 mm²7.410.0741
4.0 mm²4.610.0461
6.0 mm²3.080.0308
10 mm²1.830.0183
16 mm²1.151.910.0115
25 mm²0.7271.20.0073
35 mm²0.5240.8680.0052
50 mm²0.3870.6410.0039
70 mm²0.2680.4430.0027
95 mm²0.1930.320.0019
120 mm²0.1530.2530.0015
150 mm²0.1240.2060.0012
185 mm²0.09910.1640.0010
240 mm²0.07540.1250.0008
300 mm²0.06010.10.0006

Values are single-conductor resistances at 20 °C. For a circuit, add the relevant pair of figures together to get the loop resistance per metre (R1+R2 or R1+Rn). Aluminium is not normally used below 16 mm² in UK fixed wiring.