BS 7671 Section 701

Bathroom electrical zones

Bathrooms and rooms containing a bath or shower are treated as special locations under BS 7671. Section 701 splits them into Zone 0, Zone 1 and Zone 2 — each with its own minimum IP rating and list of accessories that may be installed. Everything below is a plain-English summary; the wiring regs remain the authoritative document.

BS 7671 Section 701 bathroom zones — Zone 0 (inside the bath or shower basin), Zone 1 (above it to 2.25 m above finished floor level) and Zone 2 (0.6 m horizontally beyond Zone 1, and 0.6 m around a wash basin tap). Tap the diagram to enlarge it.

Zone 0

Inside the bath tub or shower tray itself.

Minimum IP
IP X7 (immersion)
Allowed
Only fixed, permanently connected equipment made for Zone 0, supplied by SELV at no more than 12 V AC or 30 V ripple-free DC, with the safety source outside the zones (Reg 701.55). Mains-voltage (230 V) equipment is not permitted.
Not allowed
Sockets, switches, mains-voltage accessories of any kind.

Zone 1

Above the bath/shower tray up to 2.25 m from the floor (or above the fixed shower head if higher).

Minimum IP
IP X4 (splash) — IP X5 if a water jet is likely (public showers).
Allowed
Fixed luminaires, fans and electric showers rated for Zone 1, supplied through a 30 mA RCD.
Not allowed
Socket-outlets of any kind, including shaver supply units.

Zone 2

0.6 m horizontally outside Zone 1, up to 2.25 m from the floor. Wash basins do not create a zone of their own under the 18th Edition.

Minimum IP
IP X4 minimum.
Allowed
Luminaires and fans rated IP X4+; shaver supply units to BS EN 61558-2-5 permitted where direct spray is unlikely.
Not allowed
General 13 A socket-outlets.

Outside the zones

Everywhere else in the room.

Minimum IP
Normal indoor rating (usually IP 20).
Allowed
Standard accessories are permitted. 230 V socket-outlets must be at least 3 m horizontally from the edge of Zone 1 (Reg 701.512.3), and every circuit serving the location requires 30 mA RCD protection (Reg 701.411.3.3).
Not allowed
—

Rules that apply to the whole room

  • 30 mA RCD on every circuit serving the location — lighting, shower, towel rail, fan and any spur — Reg 701.411.3.3.
  • Supplementary bonding is only required where the general RCD/main bonding conditions of Reg 701.415.2 are not all met. In most modern installations with 30 mA RCDs and effective main bonding, supplementary bonding can be omitted.
  • Shaver sockets to BS EN 61558-2-5 (isolating transformer built in) are the only socket-type accessory permitted inside Zones 1 and 2.
  • Pull-cord switches are the traditional in-room switch; standard rocker switches must be located outside the zones (usually just outside the door).