BS 7671 Section 701

Bathroom electrical zones

Bathrooms and rooms containing a bath or shower are treated as special locations under BS 7671. Section 701 splits them into Zone 0, Zone 1 and Zone 2 — each with its own minimum IP rating and list of accessories that may be installed. Everything below is a plain-English summary; the wiring regs remain the authoritative document.

Zone 0

Inside the bath tub or shower tray itself.

Minimum IP
IP X7 (immersion)
Allowed
Only SELV ≤ 12 V AC / 30 V DC luminaires listed for Zone 0, with the safety source outside the zones.
Not allowed
Sockets, switches, mains-voltage accessories of any kind.

Zone 1

Above the bath/shower tray up to 2.25 m from the floor (or above the fixed shower head if higher).

Minimum IP
IP X4 (splash) — IP X5 if a water jet is likely (public showers).
Allowed
Fixed luminaires, fans and electric showers rated for Zone 1, supplied through a 30 mA RCD.
Not allowed
Socket-outlets (except SELV / shaver units to BS EN 61558-2-5 — see below).

Zone 2

0.6 m horizontally outside Zone 1, up to 2.25 m from the floor. Also the area around a wash basin within 0.6 m of the tap.

Minimum IP
IP X4 minimum.
Allowed
Luminaires and fans rated IP X4+; shaver sockets to BS EN 61558-2-5 permitted.
Not allowed
General 13 A socket-outlets.

Outside the zones

Everywhere else in the room.

Minimum IP
Normal indoor rating (usually IP 20).
Allowed
Standard accessories are permitted, but every circuit serving the location still requires 30 mA RCD protection (Reg 701.411.3.3).
Not allowed

Rules that apply to the whole room

  • 30 mA RCD on every circuit serving the location — lighting, shower, towel rail, fan and any spur — Reg 701.411.3.3.
  • Supplementary bonding is only required where the general RCD/main bonding conditions of Reg 701.415.2 are not all met. In most modern installations with 30 mA RCDs and effective main bonding, supplementary bonding can be omitted.
  • Shaver sockets to BS EN 61558-2-5 (isolating transformer built in) are the only socket-type accessory permitted inside Zones 1 and 2.
  • Pull-cord switches are the traditional in-room switch; standard rocker switches must be located outside the zones (usually just outside the door).