Drawing tool

Wiring diagram generator

Choose a circuit type and a consumer unit size. The tool draws the board schedule and the circuit layout — every conductor labelled with its size, the protective device rating, and the RCD requirement that applies. Download either drawing as an SVG to drop into a quote, a spec or a training sheet.

Board layout

CONSUMER UNIT — 10 USABLE WAYSMain switch + RCBO per way · Type 2 SPD at the origin · TN-C-S (PME) supply · 12-way enclosure excluding surge devicesCONSUMER UNIT · METAL ENCLOSURE · BS EN 61439-325 mm² TAILSCONTACTUM40 A30mARCBOCONTACTUM20 A30mARCBOCONTACTUM32 A30mARCBOCONTACTUM16 A30mARCBOCONTACTUM6 A30mARCBOCONTACTUM45 A30mARCBOCONTACTUM32 A30mARCBOCONTACTUM6 A30mARCBOCONTACTUM6 A30mARCBOCONTACTUM32 A30mARCBO40 ASPD100 AMAINOKT2SPD10Submain920 A radial8EV charger7Immersion6Smoke alarms5Shower4Cooker3Lighting2Lighting1Ring finalSPD supplyMain switchSurge (SPD)MAIN EARTHING TERMINAL — 16 mm² EARTHING CONDUCTOR · 10 mm² MAIN BONDING TO GAS & WATER
A typical schedule for a 10-way board with the selected circuit highlighted on way 1. An RCBO per way keeps a fault on one circuit from tripping the rest of the house.

Circuit layout & wire sizes

SOCKET OUTLETS — 32 A RING FINAL32 A Type B RCBO · 2.5 mm² / 1.5 mm² cpc · Flat twin & earth (6242Y)BOARD32 A2.5 mm² / 1.5 mm²RETURN LEG — 2.5 mm² BACK TO THE SAME TERMINALSocket 1Socket 2Socket 3Socket 4Socket 5Socket 6LINENEUTRALCPC
Socket outlets — 32 A ring final2.5 mm² / 1.5 mm² cpc on a 32 A device.

Points to watch on this circuit

  • Both legs must return to the same terminal at the board — test r1, rn and r2 end to end before energising.
  • One unfused spur per point: a single or twin socket only, taken from a socket on the ring or a junction box in the ring.
  • 2.5 mm² T&E on a 32 A ring needs a tabulated capacity of not less than 20 A (Reg 433.1.204) — check the installation method.