EICR examples

Sample EICR reports: satisfactory and unsatisfactory

Two real Electrical Installation Condition Reports we have carried out in Brighton, shared so you know exactly what you will receive. Client names, addresses and report IDs have been permanently removed.

Unsatisfactory EICR — tenanted flat, Brighton

21 pages · April 2026 · 4 boards, 21 circuits

  • Two C2 codes: unfused 100 A isolator, and a 16 mm² sub-main not protected for a 100 A supply
  • C3s: Type AC RCDs, split-load board, worn sockets, missing earthing labels
  • Shows the stated extent, sampling and limitations in Section D
Download PDF

Satisfactory EICR — commercial office, Brighton

25 pages · September 2026 · multiple boards

  • No C1, C2 or FI codes, so the installation is safe for continued use
  • C3 improvements still listed: Type AC RCDs, no SPD, fans without local isolation, labelling
  • Shows how untraceable bonds are checked with a wander lead and noted
Download PDF

What the codes mean

C1 — Danger present
Risk of injury. Immediate action — makes the report unsatisfactory.
C2 — Potentially dangerous
Urgent remedial work needed — makes the report unsatisfactory.
FI — Further investigation
Needs investigating without delay — makes the report unsatisfactory.
C3 — Improvement recommended
Not unsafe, but worth upgrading. Does not fail the report.

More detail in EICRs explained and when you need an EICR.

Common questions

What does an unsatisfactory EICR look like?

An unsatisfactory EICR has at least one observation coded C1 (danger present), C2 (potentially dangerous) or FI (further investigation required). Our sample shows two C2 codes: an unfused 100 A isolator and a 16 mm² sub-main that is not protected for the 100 A supply.

Can a satisfactory EICR still list faults?

Yes. A satisfactory report can contain C3 'improvement recommended' observations, such as Type AC RCDs or no surge protection. C3s do not make a report unsatisfactory, but they are worth planning in.

How long is an EICR valid for?

The inspector recommends the next inspection date. For private rentals the legal maximum is 5 years; for owner-occupied homes 10 years is typical.

Why do the reports say 25% sampling?

That figure records the extent stated on these particular reports, not a universal permitted minimum. A previous EICR can inform the inspector's sampling plan but does not automatically permit 25% testing. If a sample reveals defects or deterioration, the inspector should extend the relevant checks to establish their extent. BS 7671 does not prescribe fixed percentage increases; see Section D for the recorded scope and limitations.

Need an EICR in Brighton, Hove or Sussex?

NAPIT-approved, reports issued digitally, remedial quotes explained in plain English.