0–10 V dimming and wiring

An analogue control pair tells a compatible driver how bright to run. It does not dim the mains waveform, supply the LED load, or automatically switch the lights off.

For competent electricians. Generic instructions are not authority to work live. A dimmed or digitally switched-off lamp is not isolated. Identify every supply, secure isolation and prove dead with a suitable two-pole voltage indicator proved before and after use. Control buses can connect equipment on other mains circuits.

How the system works

0–10 V is an analogue command on a polarity-sensitive pair, not the driver's mains supply or LED output. In a current-sink lighting system the driver supplies the control current and the controller sinks it; in a sourcing system the controller supplies the voltage to an appropriate input. The same name does not establish compatibility. Near 10 V generally requests maximum output; low-level response, dimming curve and whether 0 V means off depend on the specific driver. One pair normally controls one group rather than individually addressed fittings.

0–10 V — polarity-sensitive analogue pairCompatible current-sink0–10 V controller exampleDriver 1 → LED load0–10 V current-sink systemDIM +DIM −Driver 2 → LED load0–10 V current-sink systemDIM +DIM −DIM +DIM −Control connections are parallel — not the LED outputs.Separate power wiring (not shown as the control bus)Protected mains L → suitably rated on/off switch or relay → each driver L; N → each driver N.CPC → required earth terminals / Class I metalwork. Never use CPC as a control conductor.
Conceptual wiring only, not a product terminal schedule. Orange lines identify the control pair, not prescribed cable colours. LED output wiring, protective devices and isolation arrangements must follow the actual design and equipment instructions.

0–10 V: 230 V power and the control pair

Two functions, not a universal requirement for two independent 230 V circuits. The lighting driver needs its rated power supply (normally 230 V AC in this UK example), while the control interface has a separate function. An electronic controller may also require a permanent 230 V line and neutral, or a specified DC supply; a passive analogue controller may need no separate operating supply. The exact controller instructions decide this.

Where the controller includes mains switching, bring the protected permanent line to its specified supply/relay input and take its switched-line output to the drivers' L terminals. Connect N to the drivers and, if required, the controller. Wire DIM+ and DIM− separately in parallel to the drivers. A controller can therefore need a permanent mains feed as well as an outgoing switched mains feed to the lamps — neither is the dimming pair. A passive controller with an integral mains switch can carry 230 V switching conductors without needing an electronic operating supply.

Only omit the operational mains relay where the specific driver and controller document dim-to-off behaviour and the design permits it. Commanded off still leaves the driver mains-powered and is not safe isolation. If the switching contact is volt-free, it does not supply 230 V by itself: wire its feed and output exactly as the manufacturer specifies. Do not link separate circuits, phases or neutrals.

230 V cable route — power is separate from the dimming signalOne protected mains circuit shown. Device terminals and cable sizes are design-dependent.Protected supply230 V ACIsolation + protectionIncoming mains cablePowered controllerLNPE*Integral rated on/off relaySwitched L to luminairesDIM+ / DIM−Switched L / N / CPC cableDriver 1 → LED loadLNPE*DIM+ / DIM−Driver 2 → LED loadLNPE*DIM+ / DIM−Brown: mains line (L)Blue: neutral (N)Green/yellow: CPC / PEOrange: separate control pair* PE to required earth terminals / Class I metalwork; maintain CPC continuity. Control colours are illustrative.
Conceptual cable-route example, not a terminal schedule. Thick grouped runs show mains L, N and CPC; the orange pair carries control only, never 230 V. The controller's relay switches line only for operational off; neutral and CPC continue through suitable terminals/junctions, not through the relay contact. Junctions must suit the cable and load. The LED outputs are not shown interconnected. Isolate all associated sources before work.

Which wiring and cable types can be used?

These are cable options, not an approved cable selection for every installation. The drawings show power and control separately for clarity; an approved combined cable is possible under the conditions below.

230 V fixed wiring
Twin-and-earth PVC or LSZH cable can provide L, N and CPC for suitable indoor fixed routes. Singles in suitable conduit/trunking are another option. Select the actual conductor size by circuit design, protection, installation method, grouping, insulation, voltage drop and fault protection — a lighting circuit is not automatically suitable for 1 or 1.5 mm².
Separate control cable
Use a dedicated two-core control cable of the insulation rating, conductor size and construction specified for the controller and drivers. Identify DIM+ and DIM− consistently at every end. Check permitted length, resistance/voltage drop, interface current and screening requirements; there is no universal 1.5 mm² or 300 m rule for analogue dimming. A screened pair is only appropriate where specified, with its screen terminated as instructed.
Combined power and control
Where equipment instructions and BS 7671 insulation/segregation rules permit, a suitable five-core mains-rated cable can carry L, N, protective earth and two control conductors. Examples include suitable fixed multicore cable or an appropriate five-core flexible connection at a fitting. Check suitability for the route and use; flexible cable is not automatically a replacement for fixed wiring. Extra permanent/switched feeds or other functions may require more cores or a separate cable.
Core identification and CPC
Keep green/yellow exclusively for protective conductors. In a five-core cable, brown can be L, blue N and green/yellow PE, with the other two cores durably identified for DA/DA or DIM+/DIM−, subject to the actual identification requirements. Do not assume black and grey are neutral. Sleeve a bare twin-and-earth CPC green/yellow at terminations; never use it as a signal wire. Twin-and-earth alone does not provide two spare control conductors.
Outdoor routes and final connections
Use cable, glands and containment suitable for moisture, UV, mechanical damage and the termination environment. SWA may suit protected external or buried routes where properly designed; armour earthing and CPC adequacy need assessment. Suitable flexible cable may serve the final luminaire connection with correct strain relief and temperature rating. LSZH describes fire/smoke characteristics, not outdoor suitability or guaranteed circuit survival in fire.
Segregation and testing
Do not assume DA or DIM terminals are SELV. Where a verified SELV/PELV analogue interface is used, preserve its required separation from mains. Sharing an enclosure, conduit or multicore is conditional on the relevant insulation and segregation rules, not simply on signal voltage. Ordinary Cat5/Cat6, alarm or bell wire must not be substituted merely because it carries a low-voltage signal. Disconnect/protect drivers and controls before insulation-resistance testing as instructed.

See the cable descriptions guide for construction examples and the circuit-design tool for its supported design checks. Neither replaces the product wiring instructions or a site-specific design.

Multiple supplies and emergency fittings

One control group or DALI bus can include equipment fed from more than one mains circuit. Identify and safely isolate every relevant source, including separately powered controllers, bus PSUs and emergency batteries, before working; label multiple supplies and provide the required isolation arrangements. Do not disconnect or bridge control wiring live. Emergency luminaires may require a permanent 230 V charging/monitoring feed as well as a switched maintained-lighting input, depending on the exact product. Do not assume a dimming command or a lighting switch isolates that permanent feed. Follow the emergency gear's wiring and testing instructions.

0–10 V: compatibility and dim-to-off

The terms are often used loosely, but sourcing/sinking behaviour, minimum level and dim-to-off capability vary. Do not mix interfaces by name alone, or add an arbitrary external voltage source to driver terminals. Ordinary phase-cut dimmers, push-to-dim inputs and DALI interfaces are different systems; only use a documented compatible interface or converter.

Wiring and commissioning sequence

  1. 1

    Identify the interface before wiring

    Check whether the driver supplies control current for a sinking controller, or expects a sourcing 0–10 V output. Both are sold as 0–10 V, but are not automatically compatible. Match polarity, voltage range, current capacity and the manufacturer's approved controller pairing; do not add an arbitrary voltage source.

  2. 2

    Plan mains power, controller power and off

    Provide the driver's rated mains L and N. Provide the controller's specified permanent mains or DC operating supply if needed, and a correctly rated switching relay unless documented dim-to-off behaviour permits operational off through the control pair. Never confuse dim-to-off with isolation.

  3. 3

    Isolate all supplies and connect

    Identify every mains circuit, controller supply and emergency battery. Secure safe isolation and prove dead. Connect the specified mains and CPC terminals; connect controller DIM+ to each driver DIM+ and DIM− to each DIM− in parallel. Keep separately controlled zones on separate pairs. LED outputs remain separate and must not be paralleled unless expressly allowed.

  4. 4

    Check insulation and segregation

    A low signal voltage does not prove SELV. Follow the actual equipment's control-terminal insulation classification and BS 7671 requirements. Only share a mains-rated multicore where the insulation, identification, terminations and manufacturer instructions permit it.

  5. 5

    Test wiring and commission the range

    Disconnect/protect sensitive electronics for installation testing as instructed. Reconnect, energise safely and check maximum output, minimum output, smooth dimming and actual off behaviour. Set supported low/high trims and verify relay operation, restart behaviour and control-failure response. Never short the pair live as an improvised test.

Common fault checks

All lamps stay bright: check the correct input type, pair continuity, polarity and controller operation; an open pair commonly produces maximum output, but confirm the driver instructions. Lamps reach minimum but will not turn off: check the separate switching function. Uneven dimming: check mixed driver types and their minimum levels. Never short or disconnect the pair live as an improvised diagnostic procedure.

Where it makes sense

Commercial or architectural schemes needing straightforward group-level control, including compatible bulkheads, panels and linear luminaires. An extra control pair normally needs planning at installation or a suitable existing cable route; it is not a direct replacement for a two-wire domestic dimmer.

Paul's products: do not assume every Kosnic DD lamp, Blanca fitting, BELL tube or Aurora lamp accepts this interface. Confirm the exact driver/module code and accessories first. A Blanca enclosure alone does not determine the dimming system.

Verified sources and limitations

BS 7671:2018+A4:2026, Chapter 52 (wiring systems), Chapter 53 (isolation, switching and control) and Part 6 (verification) provide the installation framework. This guide is not the licensed standard or a universal terminal diagram; consult the applicable edition and current instructions for every installed product. No printed page numbers are assumed.