Ohm's Law for electricians,
on the job.

V = I × R is more than a formula from college. It explains almost every reading on your tester — continuity, loop impedance, insulation resistance and voltage drop. Here are seven worked examples from real work.

V = I × R

Voltage from current and resistance

I = V ÷ R

Current from voltage and resistance

R = V ÷ I

Resistance from voltage and current

P = V × I = I²R = V²/R

Power, three ways

Worked examples

Seven ways you use it every week.

1. Is the immersion element sound?

The job: Immersion heater not heating. Circuit isolated, proved dead and locked off; element terminals disconnected and measured with a low-resistance ohmmeter.

Rated 3 kW at 230 V: R = V² ÷ P = 230² ÷ 3,000 ≈ 17.6 Ω

(If rated 3 kW at 240 V: 240² ÷ 3,000 = 19.2 Ω)

Expected current: I = 230 ÷ 17.6 ≈ 13.0 A

What it tells you: A reading near the calculated value suggests the element is continuous. Open circuit (OL) means a broken element; a reading far below it suggests a short. An element can still have an insulation fault to earth, so carry out an insulation resistance test too. Check the rating plate — elements are sold at both 230 V and 240 V ratings.

2. Ring final end-to-end readings

The job: 50 m ring in 2.5/1.5 mm² twin and earth. End-to-end continuity of each conductor measured at the board.

Copper at 20 °C: 2.5 mm² ≈ 7.41 mΩ/m, 1.5 mm² ≈ 12.10 mΩ/m

r1 = 50 × 0.00741 ≈ 0.37 Ω rn ≈ 0.37 Ω

r2 = 50 × 0.0121 ≈ 0.61 Ω (r2 ≈ 1.67 × r1)

Cross-connected R1 + R2 at each socket ≈ (r1 + r2) ÷ 4 ≈ 0.24 Ω

What it tells you: Line and neutral ends should match closely and the CPC should be about 1.67 times higher for 2.5/1.5 cable. A socket reading noticeably higher than the rest points to a spur or a poor connection at that point.

3. Voltage drop is Ohm's Law on the cable

The job: 20 A load at the end of a 25 m radial in 2.5 mm² twin and earth.

Tabulated voltage drop for 2.5 mm² T&E: 18 mV/A/m

VD = 18 × 20 × 25 ÷ 1,000 = 9 V

9 ÷ 230 ≈ 3.9%

What it tells you: Within the 5% figure for circuits other than lighting given in BS 7671:2018+A4:2026 (previous A2:2022+A3:2024 version also current until 15 October 2026) Appendix 4 for a public LV supply (3% for lighting). The mV/A/m value is just the cable's resistance (and reactance) for both conductors, so this is V = I × R in disguise. Check the figures for your cable and installation method.

4. Fault current and disconnection

The job: Measured Zs of 1.20 Ω on a socket circuit protected by a Type B 32 A device.

Prospective earth fault current ≈ U0 ÷ Zs = 230 ÷ 1.20 ≈ 192 A

Type B needs 5 × In = 160 A to trip instantaneously

Tabulated max Zs uses U0 × Cmin: 230 × 0.95 ÷ 160 ≈ 1.37 Ω

What it tells you: 1.20 Ω is below 1.37 Ω, but remember a measured value is taken cold — compare against the corrected (typically 80%) rule-of-thumb figures used for verification, not just the table maximum.

5. What an insulation resistance reading means

The job: Insulation resistance test at 500 V DC between live conductors and earth.

At 1 MΩ: I = 500 ÷ 1,000,000 = 0.5 mA

At 300 MΩ: I = 500 ÷ 300,000,000 ≈ 1.7 µA

Circuits in parallel combine: two circuits at 2 MΩ each read 1 MΩ together

What it tells you: 1 MΩ is the minimum in Table 64 for 500 V tests, but a healthy new circuit normally reads hundreds of MΩ. A low whole-board reading may be several circuits in parallel — split them to find the culprit. Disconnect sensitive equipment, SPDs and electronics before testing.

6. Why a heater gives less heat on a low supply

The job: Customer says a 3 kW (230 V rated) heater feels weaker. Supply measured at 216 V.

P = V² ÷ R, with R fixed ≈ 17.6 Ω

216² ÷ 17.6 ≈ 2,650 W

About 12% less heat for a 6% fall in voltage

What it tells you: Power on a resistive load varies with the square of voltage, so small voltage changes have a noticeable effect. A persistently low supply voltage is a matter for the network operator.

7. Finding a high-resistance joint

The job: Socket reads 238 V with nothing plugged in, falling to 226 V when a 10 A heater is switched on.

Voltage lost = 238 − 226 = 12 V

Resistance in the line–neutral path ≈ 12 ÷ 10 = 1.2 Ω

Heat in that resistance: P = I² × R = 10² × 1.2 = 120 W

What it tells you: That much drop on a short domestic circuit is excessive and suggests a loose or burnt connection somewhere in the circuit or supply. 120 W concentrated in one terminal can char an accessory — isolate and trace it. Live voltage readings must be taken with a suitable approved voltage indicator or multimeter and GS38-compliant leads.

Where Ohm's Law misleads

  • Motors, LED drivers and electronics have impedance, power factor and inrush — a cold resistance reading won't give running current.
  • Conductor resistance rises as cable warms; test readings are cold.
  • Filament lamps read far lower cold than when lit.
  • Parallel paths (bonding, other circuits) can make readings look better than the conductor you think you're measuring.

Safety first

Resistance measurements are taken dead: isolate, lock off and prove dead with a proven approved voltage indicator first. Live tests use suitable instruments and GS38 leads. Figures here are worked illustrations — check manufacturer data and BS 7671:2018+A4:2026 (previous A2:2022+A3:2024 version also current until 15 October 2026) tables for real design decisions.

Questions

What is Ohm's Law?

Voltage equals current multiplied by resistance (V = I × R). Rearranged, I = V ÷ R and R = V ÷ I. Combined with power (P = V × I) it gives P = I² × R and P = V² ÷ R.

Does Ohm's Law work for every load?

It holds exactly for resistive loads such as heater and immersion elements. Motors, LED drivers and electronic loads have impedance, power factor and inrush, so a simple V ÷ R from a cold resistance reading will not predict their running current.

Why do resistance readings change when cable warms up?

Copper resistance rises with temperature (roughly 0.4% per °C). Test readings are taken cold, so design and verification figures allow for conductors reaching operating temperature.

Should I measure resistance on a live circuit?

No. Continuity and element resistance are measured with the circuit safely isolated, proved dead and locked off. Live readings such as loop impedance and voltage use instruments and leads suitable for the task, following HSE GS38.