Equipotential bonding,
explained and checked.

Bonding doesn't stop a fault — it limits the voltage between things you can touch at the same time while the protective device clears it. Here's what needs bonding, how to decide, and how to prove it works.

The idea

Equal potential, not "earthing".

In an earth fault, the main earthing terminal and everything connected to it rise above true Earth for a moment. A metal pipe that still sits at Earth potential would then have a dangerous voltage between it and a faulty appliance. Protective equipotential bonding connects those parts together so they rise together, keeping touch voltage low inside the "equipotential zone" — the building. That is why bonding is about connecting extraneous parts, and why its value depends on the automatic disconnection that follows.

Types of bonding

Four terms, four jobs.

Reg 411.3.1.2

Protective (main) bonding

Connects extraneous-conductive-parts entering the building — metallic water, gas and oil service pipes, other metallic services, accessible structural steel and central-heating/air-conditioning systems where extraneous — to the main earthing terminal.

Reg 415.2

Supplementary bonding

Local bonding linking simultaneously accessible exposed- and extraneous-conductive-parts in one location. An additional protection measure, used where disconnection times can't be met or a special location requires it.

Section 545

Functional bonding / earthing

Connections made for the correct operation of equipment, not for shock protection. Amendment 4:2026 added Section 545, covering functional earthing and functional-equipotential-bonding for ICT equipment and systems: pink 'FE' sleeving, segregation from the protective earth, 2.5–4 mm² copper conductors and a target resistance of 2 Ω or less. Must not be relied on as, or confused with, protective bonding.

Reg 418.2

Earth-free local equipotential bonding

A special measure where parts are bonded together but deliberately not to Earth. Only for installations under effective supervision by skilled or instructed persons — not domestic work.

Classification

Does this part need bonding?

An extraneous-conductive-part is defined in BS 7671:2018+A4:2026 (previous A2:2022+A3:2024 version also current until 15 October 2026) Part 2 as a conductive part liable to introduce a potential, generally Earth potential, and not forming part of the electrical installation. Work through it in order:

  1. 1. Is it conductive and not part of the electrical installation?

    Exposed-conductive-parts (metal cases of Class I equipment) are earthed by circuit protective conductors, not bonded as extraneous parts.

  2. 2. Can it introduce a potential?

    Ask whether it is connected to Earth or another potential from outside the equipotential zone — a metal service pipe entering the ground, structural steel in contact with the ground, or metalwork linked to another building.

  3. 3. Check how it enters and connects

    Trace pipework back: a plastic incoming service with metal pipework inside may not make the internal pipes extraneous. Watch for plastic sections, push-fit fittings and replaced runs.

  4. 4. If in doubt, measure — and interpret carefully

    A resistance test between the part and the main earthing terminal helps the assessment. A commonly used approach compares the reading against a body-current threshold (see the worked example and calculator on the extraneous-conductive-parts page). It informs your judgement; it is not a BS 7671 pass/fail limit.

  5. 5. Record the decision

    Note what was bonded, what was assessed as not extraneous, and why — on the certificate, schedule or EICR observations.

Inspection & testing

Checks that prove bonding is effective.

Conductor size — main bonding (TN-S / TT)

Reg 544.1.1: at least half the cross-sectional area of the main earthing conductor, with an absolute minimum of 6 mm² copper (25 mm² maximum required).

Conductor size — main bonding (TN-C-S / PME)

On PME supplies Table 54.8 applies instead of the half-earthing-conductor rule: minimum 10 mm² copper (or equivalent) regardless of the size of the supply neutral/PEN conductor, or as sized from Table 54.8 for larger supplies.

Connection position

Reg 544.1.2: as near as practicable to the point of entry of the service, on the consumer's side of any meter or insulating insert and before any branch pipework. Use BS 951 clamps with the 'Safety Electrical Connection — Do Not Remove' label.

Conductor size — supplementary bonding

Reg 544.2, sized from the circuit protective conductor: between two exposed-conductive-parts, not smaller than the smaller CPC of the circuits concerned; between an exposed- and an extraneous-conductive-part, at least half the CPC of that exposed part; between two extraneous parts (e.g. pipe to pipe), 2.5 mm² copper if mechanically protected, 4 mm² if not. In bathrooms, 4 mm² green/yellow is typical where exposed, 2.5 mm² where concealed and protected.

Continuity of main bonding

Dead test with a low-resistance ohmmeter between the clamp and the main earthing terminal (or with long leads, wandering-lead method). IET guidance generally expects a very low value, of the order of 0.05 Ω for main bonding conductors; investigate anything markedly higher.

Effectiveness of supplementary bonding

Reg 415.2.2: R ≤ 50 V ÷ Ia between simultaneously accessible parts, where Ia is the current that operates the protective device within the required time. For RCD protection Ia is IΔn — e.g. 50 ÷ 0.03 = 1,667 Ω.

Visual inspection

Clamps tight, correct type, labelled, not painted over or corroded; conductor green-and-yellow, continuous (looped without cutting where looped), not reliant on pipework joints with plastic inserts.

Regulation numbers refer to BS 7671:2018+A4:2026 (previous A2:2022+A3:2024 version also current until 15 October 2026). Confirm exact wording and tables in your copy of the standard and IET Guidance Note 3; page numbers are deliberately not quoted.

Never disconnect bonding casually

On TN-C-S (PME) supplies a broken or high-resistance PEN conductor can push neutral current through bonding conductors and pipework. Removing a clamp can break that path under load. Isolate the installation where possible, test the conductor for current with a clamp meter and for voltage with a proven contact-type voltage indicator, and fit a temporary bridge before disconnecting anything.

Diverted neutral faults

Questions

Is bonding the same as earthing?

No. Earthing connects exposed-conductive-parts of electrical equipment to the main earthing terminal so a fault operates the protective device. Bonding connects conductive parts together (and to the main earthing terminal) so that, during a fault, the voltage between parts someone could touch at the same time stays low.

Does every metal pipe need bonding?

No. Only extraneous-conductive-parts need protective bonding — parts liable to introduce a potential, generally Earth potential, into the installation. Metal pipework fed by a plastic service pipe, or isolated sections of metal, may not be extraneous. The decision is a documented assessment, not a rule that all metal gets a clamp.

Can I remove an old bonding conductor if I decide it isn't needed?

Not casually. On PME supplies, bonding conductors can carry diverted neutral current, and disconnecting one can expose you to a dangerous voltage or arc. Treat any bonding conductor as potentially live until proven otherwise and follow safe-isolation practice.

Is supplementary bonding still needed in bathrooms?

Not always. BS 7671 Section 701 allows it to be omitted where all the listed conditions are met, including 30 mA RCD protection for all circuits of the location and effective main protective bonding of the relevant extraneous parts. Where any condition isn't met, it is required.