Skip to main content
EMERGENCY HELP!
All calculators

Inspection & test

Earth fault loop & prospective fault current

Combines Ze at origin with the R1+R2 of the final circuit to give Zs, and calculates the prospective fault current at both the origin and the far end of the circuit. Compare Ipf at the origin against the breaking capacity of every protective device downstream.

Calculator inputs & results

Results

Calculated Zs0.80Ω
Ipf at origin (from Ze)0.66kA
Ipf at far end (from Zs)0.29kA